Minco Temptran Rangeable Temperature Transmitter and Housing
Minco TT829PD1M Temptran Rangeable Temperature Transmitter and Housing. This industrial-grade, loop-powered temperature transmitter converts a low-level RTD sensor signal into a highly stable, linearized 4-20 mA DC output for long-distance data transmission. Integrated into a ruggedized field enclosure, it is engineered to eliminate signal degradation and electrical noise interference in harsh building automation and industrial process environments.
- MPN / Catalog Model: TT829PD1M (Base Series: TT829; Sensor Input Code: PD; Output Code: 1; Range Code: M).
- Manufacturer & Line: Minco Products, Inc. (Temptran™ Transmitter Line).
- Quantity & Packaging / Form Factor: Single transmitter unit enclosed in a durable, wall- or surface-mountable field housing. Typically features standard 1/2" NPT integral conduit bosses and a gasketed cover for secure, weather-tight environmental sealing.
- Material Construction / Metallurgy: The protective enclosure is constructed from a rugged die-cast alloy or high-impact industrial plastic designed for moisture resistance. The internal transmitter electronics are epoxy-potted to resist mechanical vibration, physical shock, and condensation.
- Technical Specifications & Tolerances: Operates on a 2-wire loop-powered architecture with a typical supply voltage range of 8.5 to 35 VDC. The PD designation indicates strict compatibility with 100 Ohm Platinum RTDs (0.00385 Ω/Ω/°C TCR, matching DIN EN 60751 / IEC 751 Class B standards). Delivers a standard 4-20 mA analog output corresponding to the specific factory-calibrated "M" temperature range, featuring internal potentiometers for field-adjustable zero and span calibrations.
- Hardware & System Compatibility: Interfaces seamlessly with standard PLC, DCS, SCADA, and BAS (Building Automation System) control panels via non-polar screw terminal blocks (accepting AWG 22 to 14 wiring). Universally compatible with standard industrial 100Ω Platinum RTD probes.
- Standards, Cleanliness & Purity: Housing is designed to meet standard industrial NEMA / IP environmental protection ratings for outdoor or mechanical room installations. Provides exceptional ambient temperature stability, typically rated for -40°C to 85°C (-40°F to 185°F) operating environments with minimal thermal drift.
- Primary Application: HVAC (Heating, Ventilation, and Air Conditioning) duct and ambient temperature monitoring, chiller/boiler process control, refrigeration loops, and general industrial automation where reliable, noise-immune, long-distance RTD signal routing is essential.
used; in excellent condition
Please note that Life Sciences Trading is not a factory-authorized distributor of the products listed in this store. The items have been acquired as surplus from leading life sciences companies.