{"product_id":"minco-temptran-rangeable-temperature-transmitter-and-housing","title":"Minco Temptran Rangeable Temperature Transmitter and Housing","description":"\u003cp\u003e\u003cb\u003eMinco TT829PD1M Temptran Rangeable Temperature Transmitter and Housing\u003c\/b\u003e. This industrial-grade, loop-powered temperature transmitter converts a low-level RTD sensor signal into a highly stable, linearized 4-20 mA DC output for long-distance data transmission. Integrated into a ruggedized field enclosure, it is engineered to eliminate signal degradation and electrical noise interference in harsh building automation and industrial process environments.\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cb\u003eMPN \/ Catalog Model:\u003c\/b\u003e TT829PD1M (Base Series: TT829; Sensor Input Code: PD; Output Code: 1; Range Code: M).\u003c\/li\u003e\n\u003cli\u003e\n\u003cb\u003eManufacturer \u0026amp; Line:\u003c\/b\u003e Minco Products, Inc. (Temptran™ Transmitter Line).\u003c\/li\u003e\n\u003cli\u003e\n\u003cb\u003eQuantity \u0026amp; Packaging \/ Form Factor:\u003c\/b\u003e Single transmitter unit enclosed in a durable, wall- or surface-mountable field housing. Typically features standard 1\/2\" NPT integral conduit bosses and a gasketed cover for secure, weather-tight environmental sealing.\u003c\/li\u003e\n\u003cli\u003e\n\u003cb\u003eMaterial Construction \/ Metallurgy:\u003c\/b\u003e The protective enclosure is constructed from a rugged die-cast alloy or high-impact industrial plastic designed for moisture resistance. The internal transmitter electronics are epoxy-potted to resist mechanical vibration, physical shock, and condensation.\u003c\/li\u003e\n\u003cli\u003e\n\u003cb\u003eTechnical Specifications \u0026amp; Tolerances:\u003c\/b\u003e Operates on a 2-wire loop-powered architecture with a typical supply voltage range of 8.5 to 35 VDC. The \u003cb\u003ePD\u003c\/b\u003e designation indicates strict compatibility with 100 Ohm Platinum RTDs (0.00385 Ω\/Ω\/°C TCR, matching DIN EN 60751 \/ IEC 751 Class B standards). Delivers a standard 4-20 mA analog output corresponding to the specific factory-calibrated \"M\" temperature range, featuring internal potentiometers for field-adjustable zero and span calibrations.\u003c\/li\u003e\n\u003cli\u003e\n\u003cb\u003eHardware \u0026amp; System Compatibility:\u003c\/b\u003e Interfaces seamlessly with standard PLC, DCS, SCADA, and BAS (Building Automation System) control panels via non-polar screw terminal blocks (accepting AWG 22 to 14 wiring). Universally compatible with standard industrial 100Ω Platinum RTD probes.\u003c\/li\u003e\n\u003cli\u003e\n\u003cb\u003eStandards, Cleanliness \u0026amp; Purity:\u003c\/b\u003e Housing is designed to meet standard industrial NEMA \/ IP environmental protection ratings for outdoor or mechanical room installations. Provides exceptional ambient temperature stability, typically rated for -40°C to 85°C (-40°F to 185°F) operating environments with minimal thermal drift.\u003c\/li\u003e\n\u003cli\u003e\n\u003cb\u003ePrimary Application:\u003c\/b\u003e HVAC (Heating, Ventilation, and Air Conditioning) duct and ambient temperature monitoring, chiller\/boiler process control, refrigeration loops, and general industrial automation where reliable, noise-immune, long-distance RTD signal routing is essential.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003chr\u003e\n\u003cp\u003e\u003cstrong\u003eused; in excellent condition\u003c\/strong\u003e\u003c\/p\u003e","brand":"Minco","offers":[{"title":"Default Title","offer_id":68239266971900,"sku":"7049","price":61.75,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0627\/8463\/5132\/files\/minco-temptran-rangeable-temperature-transmitter-and-housing-other-leads-probes-minco-287648.jpg?v=1795470086","url":"https:\/\/lifesciencestrading.com\/products\/minco-temptran-rangeable-temperature-transmitter-and-housing","provider":"Life Sciences Trading","version":"1.0","type":"link"}